AuditLok XL 2008 - Door Configuration
ExistsElectronics will ignore all door hardware and software settings until the door "exists" in the system.Administrator Only: 1. Log in. 2. Select “FACTORY”. 3. Select “DOORS”. 4. Scroll left or right as needed to select the door to setup. 5. Select “EXISTS” to toggle between "YES" or "NO". 6. Select "DONE". SensorsOuter doors normally have two sensors. Inner doors normally have one sensor.Administrator Only: 1. Log in. 2. Select “FACTORY”. 3. Select “DOORS”. 4. Scroll left or right as needed to select the door to setup. 5. Select “SENSORS” to toggle between "1" or "1 & 2" or "NONE". 6. Select "DONE". Behind & Dual KeyAn inner door must be set behind the correct outer door. An outer door must be set behind NONE. Enable DUAL KEY only if the customer requires two users for access to the compartment. One line on the screen controls both the Behind and the Dual features.Administrator Only: 1. Log in. 2. Select “FACTORY”. 3. Select “DOORS”. 4. Scroll left or right as needed to select the door to setup. 5. Select “BEHIND/DUAL” to toggle between door numbers (BEHIND) and "YES" or "NO" (DUAL). 6. Select "DONE". |
|